3ph 690V to 415V Isolation Transformers
690V is the standard output of most grid-scale battery inverters, and it’s common on large drives and mining installations. Almost nothing you need to run alongside that equipment works at 690 V.
Thermal management, fire detection and suppression, controls and SCADA, lighting, small power, comms, security, pumps — all of it is 415 V and 240 V equipment. Something has to bridge the two, and on a site where the auxiliary system is what keeps the main asset alive, that something should not be an afterthought.
The SD690 range is a three-phase dry-type isolation transformer that cleanly converts 690V to 415V four-wire supply with a neutral.

Below is a reference table of standard sizes, typically requested by customers. Other kVA ratings available on request.
| Part number | Rating | Input | Output | Configuration | Specifications |
|---|---|---|---|---|---|
| SD690-50kVA-3I | 50 kVA | 690 V @ 41.8 A | 415 V @ 69.6 A | Dyn11 3-wire Delta / 4-wire StarOther available on request | |
Part numberSD690-50kVA-3I Rating50 kVA Input3-phase 690 V @ 41.8 A Output3-phase 415 V @ 69.6 A EnclosureIP23 indoorIP65 outdoor Dimensions H × W × D1080 × 760 × 660 mm1500 × 950 × 750 mm Mass424 kg577 kg Also available open-type (IP00). Air-forced (AF) cooling available where the footprint has to come down. We quote indoor and outdoor together so you can compare size and price before you decide. Construction. Three-phase dry-type isolation transformer with enamelled copper windings and drilled copper bar terminals mounted at the bottom of the unit for cable longevity. Neutral available on the output for connection if required. Brass earth stud provided for connection. Supplied open (IP00), or fitted inside a powder-coated steel enclosure — vented for indoor (IP23) or sealed for outdoor (IP65) use, with panels to access terminals for hardwiring. ConfigurationDyn11 · 3-wire Delta to 4-wire StarOther available on request InsulationClass H — 180 °C StandardsAS/NZS 60076 AS/NZS 61558 Warranty5 years standard Lead Time GuaranteeConfirmed on order Australian madeBuilt in Dandenong South Options. Electrostatic screen led to an isolated terminal (typically recommended), ±2.5% and ±5% off-load tappings, winding temperature sensors, air-forced cooling, side gland plate, IP66 wiring chamber. Sends the part number and rating with your enquiry. | |||||
| SD690-100kVA-3I | 100 kVA | 690 V @ 83.7 A | 415 V @ 139 A | Dyn11 3-wire Delta / 4-wire StarOther available on request | |
Part numberSD690-100kVA-3I Rating100 kVA Input3-phase 690 V @ 83.7 A Output3-phase 415 V @ 139 A EnclosureIP23 indoorIP65 outdoor Dimensions H × W × D1300 × 775 × 700 mm1650 × 1000 × 950 mm Mass651 kg755 kg Also available open-type (IP00). Air-forced (AF) cooling available where the footprint has to come down. We quote indoor and outdoor together so you can compare size and price before you decide. Construction. Three-phase dry-type isolation transformer with enamelled copper windings and drilled copper bar terminals mounted at the bottom of the unit for cable longevity. Neutral available on the output for connection if required. Brass earth stud provided for connection. Supplied open (IP00), or fitted inside a powder-coated steel enclosure — vented for indoor (IP23) or sealed for outdoor (IP65) use, with panels to access terminals for hardwiring. ConfigurationDyn11 · 3-wire Delta to 4-wire StarOther available on request InsulationClass H — 180 °C StandardsAS/NZS 60076 AS/NZS 61558 Warranty5 years standard Lead Time GuaranteeConfirmed on order Australian madeBuilt in Dandenong South Options. Electrostatic screen led to an isolated terminal (typically recommended), ±2.5% and ±5% off-load tappings, winding temperature sensors, air-forced cooling, side gland plate, IP66 wiring chamber. Sends the part number and rating with your enquiry. | |||||
| SD690-150kVA-3I | 150 kVA | 690 V @ 126 A | 415 V @ 209 A | Dyn11 3-wire Delta / 4-wire StarOther available on request | |
Part numberSD690-150kVA-3I Rating150 kVA Input3-phase 690 V @ 126 A Output3-phase 415 V @ 209 A EnclosureIP23 indoorIP65 outdoor Dimensions H × W × D1300 × 775 × 700 mm1900 × 1350 × 1150 mm Mass810 kg1199 kg Also available open-type (IP00). Air-forced (AF) cooling available where the footprint has to come down. We quote indoor and outdoor together so you can compare size and price before you decide. Construction. Three-phase dry-type isolation transformer with enamelled copper windings and drilled copper bar terminals mounted at the bottom of the unit for cable longevity. Neutral available on the output for connection if required. Brass earth stud provided for connection. Supplied open (IP00), or fitted inside a powder-coated steel enclosure — vented for indoor (IP23) or sealed for outdoor (IP65) use, with panels to access terminals for hardwiring. ConfigurationDyn11 · 3-wire Delta to 4-wire StarOther available on request InsulationClass H — 180 °C StandardsAS/NZS 60076 AS/NZS 61558 Warranty5 years standard Lead Time GuaranteeConfirmed on order Australian madeBuilt in Dandenong South Options. Electrostatic screen led to an isolated terminal (typically recommended), ±2.5% and ±5% off-load tappings, winding temperature sensors, air-forced cooling, side gland plate, IP66 wiring chamber. Sends the part number and rating with your enquiry. | |||||
| SD690-200kVA-3I | 200 kVA | 690 V @ 167 A | 415 V @ 278 A | Dyn11 3-wire Delta / 4-wire StarOther available on request | |
Part numberSD690-200kVA-3I Rating200 kVA Input3-phase 690 V @ 167 A Output3-phase 415 V @ 278 A EnclosureIP23 indoorIP65 outdoor Dimensions H × W × D1500 × 900 × 770 mm1900 × 1350 × 1150 mm Mass1142 kg1474 kg Also available open-type (IP00). Air-forced (AF) cooling available where the footprint has to come down. We quote indoor and outdoor together so you can compare size and price before you decide. Construction. Three-phase dry-type isolation transformer with enamelled copper windings and drilled copper bar terminals mounted at the bottom of the unit for cable longevity. Neutral available on the output for connection if required. Brass earth stud provided for connection. Supplied open (IP00), or fitted inside a powder-coated steel enclosure — vented for indoor (IP23) or sealed for outdoor (IP65) use, with panels to access terminals for hardwiring. ConfigurationDyn11 · 3-wire Delta to 4-wire StarOther available on request InsulationClass H — 180 °C StandardsAS/NZS 60076 AS/NZS 61558 Warranty5 years standard Lead Time GuaranteeConfirmed on order Australian madeBuilt in Dandenong South Options. Electrostatic screen led to an isolated terminal (typically recommended), ±2.5% and ±5% off-load tappings, winding temperature sensors, air-forced cooling, side gland plate, IP66 wiring chamber. Sends the part number and rating with your enquiry. | |||||
| SD690-250kVA-3I | 250 kVA | 690 V @ 209 A | 415 V @ 348 A | Dyn11 3-wire Delta / 4-wire StarOther available on request | |
Part numberSD690-250kVA-3I Rating250 kVA Input3-phase 690 V @ 209 A Output3-phase 415 V @ 348 A EnclosureIP23 indoorIP65 outdoor Dimensions H × W × D1500 × 900 × 770 mm1900 × 1350 × 1150 mm Mass1454 kg1618 kg Also available open-type (IP00). Air-forced (AF) cooling available where the footprint has to come down. We quote indoor and outdoor together so you can compare size and price before you decide. Construction. Three-phase dry-type isolation transformer with enamelled copper windings and drilled copper bar terminals mounted at the bottom of the unit for cable longevity. Neutral available on the output for connection if required. Brass earth stud provided for connection. Supplied open (IP00), or fitted inside a powder-coated steel enclosure — vented for indoor (IP23) or sealed for outdoor (IP65) use, with panels to access terminals for hardwiring. ConfigurationDyn11 · 3-wire Delta to 4-wire StarOther available on request InsulationClass H — 180 °C StandardsAS/NZS 60076 AS/NZS 61558 Warranty5 years standard Lead Time GuaranteeConfirmed on order Australian madeBuilt in Dandenong South Options. Electrostatic screen led to an isolated terminal (typically recommended), ±2.5% and ±5% off-load tappings, winding temperature sensors, air-forced cooling, side gland plate, IP66 wiring chamber. Sends the part number and rating with your enquiry. | |||||
| SD690-300kVA-3I | 300 kVA | 690 V @ 251 A | 415 V @ 417 A | Dyn11 3-wire Delta / 4-wire StarOther available on request | |
Part numberSD690-300kVA-3I Rating300 kVA Input3-phase 690 V @ 251 A Output3-phase 415 V @ 417 A EnclosureIP23 indoorIP65 outdoor Dimensions H × W × D1600 × 900 × 970 mm1900 × 1350 × 1150 mm Mass1567 kg1606 kg Also available open-type (IP00). Air-forced (AF) cooling available where the footprint has to come down. We quote indoor and outdoor together so you can compare size and price before you decide. Construction. Three-phase dry-type isolation transformer with enamelled copper windings and drilled copper bar terminals mounted at the bottom of the unit for cable longevity. Neutral available on the output for connection if required. Brass earth stud provided for connection. Supplied open (IP00), or fitted inside a powder-coated steel enclosure — vented for indoor (IP23) or sealed for outdoor (IP65) use, with panels to access terminals for hardwiring. ConfigurationDyn11 · 3-wire Delta to 4-wire StarOther available on request InsulationClass H — 180 °C StandardsAS/NZS 60076 AS/NZS 61558 Warranty5 years standard Lead Time GuaranteeConfirmed on order Australian madeBuilt in Dandenong South Options. Electrostatic screen led to an isolated terminal (typically recommended), ±2.5% and ±5% off-load tappings, winding temperature sensors, air-forced cooling, side gland plate, IP66 wiring chamber. Sends the part number and rating with your enquiry. | |||||
| SD690-400kVA-3I | 400 kVA | 690 V @ 335 A | 415 V @ 556 A | Dyn11 3-wire Delta / 4-wire StarOther available on request | |
Part numberSD690-400kVA-3I Rating400 kVA Input3-phase 690 V @ 335 A Output3-phase 415 V @ 556 A EnclosureIP23 indoorIP65 outdoor Dimensions H × W × D1750 × 1100 × 950 mm2200 × 1500 × 1250 mm Mass1807 kg2045 kg Also available open-type (IP00). Air-forced (AF) cooling available where the footprint has to come down. We quote indoor and outdoor together so you can compare size and price before you decide. Construction. Three-phase dry-type isolation transformer with enamelled copper windings and drilled copper bar terminals mounted at the bottom of the unit for cable longevity. Neutral available on the output for connection if required. Brass earth stud provided for connection. Supplied open (IP00), or fitted inside a powder-coated steel enclosure — vented for indoor (IP23) or sealed for outdoor (IP65) use, with panels to access terminals for hardwiring. ConfigurationDyn11 · 3-wire Delta to 4-wire StarOther available on request InsulationClass H — 180 °C StandardsAS/NZS 60076 AS/NZS 61558 Warranty5 years standard Lead Time GuaranteeConfirmed on order Australian madeBuilt in Dandenong South Options. Electrostatic screen led to an isolated terminal (typically recommended), ±2.5% and ±5% off-load tappings, winding temperature sensors, air-forced cooling, side gland plate, IP66 wiring chamber. Sends the part number and rating with your enquiry. | |||||
| SD690-500kVA-3I | 500 kVA | 690 V @ 418 A | 415 V @ 696 A | Dyn11 3-wire Delta / 4-wire StarOther available on request | |
Part numberSD690-500kVA-3I Rating500 kVA Input3-phase 690 V @ 418 A Output3-phase 415 V @ 696 A EnclosureIP23 indoorIP65 outdoor Dimensions H × W × D1750 × 1100 × 950 mmOn request Mass2015 kgOn request Also available open-type (IP00). Air-forced (AF) cooling available where the footprint has to come down. We quote indoor and outdoor together so you can compare size and price before you decide. Construction. Three-phase dry-type isolation transformer with enamelled copper windings and drilled copper bar terminals mounted at the bottom of the unit for cable longevity. Neutral available on the output for connection if required. Brass earth stud provided for connection. Supplied open (IP00), or fitted inside a powder-coated steel enclosure — vented for indoor (IP23) or sealed for outdoor (IP65) use, with panels to access terminals for hardwiring. ConfigurationDyn11 · 3-wire Delta to 4-wire StarOther available on request InsulationClass H — 180 °C StandardsAS/NZS 60076 AS/NZS 61558 Warranty5 years standard Lead Time GuaranteeConfirmed on order Australian madeBuilt in Dandenong South Options. Electrostatic screen led to an isolated terminal (typically recommended), ±2.5% and ±5% off-load tappings, winding temperature sensors, air-forced cooling, side gland plate, IP66 wiring chamber. Sends the part number and rating with your enquiry. | |||||
| SD690-600kVA-3I | 600 kVA | 690 V @ 502 A | 415 V @ 835 A | Dyn11 3-wire Delta / 4-wire StarOther available on request | |
Part numberSD690-600kVA-3I Rating600 kVA Input3-phase 690 V @ 502 A Output3-phase 415 V @ 835 A EnclosureIP23 indoorIP65 outdoor Dimensions H × W × D1750 × 1100 × 950 mmOn request Mass2367 kgOn request Also available open-type (IP00). Air-forced (AF) cooling available where the footprint has to come down. We quote indoor and outdoor together so you can compare size and price before you decide. Construction. Three-phase dry-type isolation transformer with enamelled copper windings and drilled copper bar terminals mounted at the bottom of the unit for cable longevity. Neutral available on the output for connection if required. Brass earth stud provided for connection. Supplied open (IP00), or fitted inside a powder-coated steel enclosure — vented for indoor (IP23) or sealed for outdoor (IP65) use, with panels to access terminals for hardwiring. ConfigurationDyn11 · 3-wire Delta to 4-wire StarOther available on request InsulationClass H — 180 °C StandardsAS/NZS 60076 AS/NZS 61558 Warranty5 years standard Lead Time GuaranteeConfirmed on order Australian madeBuilt in Dandenong South Options. Electrostatic screen led to an isolated terminal (typically recommended), ±2.5% and ±5% off-load tappings, winding temperature sensors, air-forced cooling, side gland plate, IP66 wiring chamber. Sends the part number and rating with your enquiry. | |||||
| SD690-750kVA-3I | 750 kVA | 690 V @ 628 A | 415 V @ 1043 A | Dyn11 3-wire Delta / 4-wire StarOther available on request | |
Part numberSD690-750kVA-3I Rating750 kVA Input3-phase 690 V @ 628 A Output3-phase 415 V @ 1043 A EnclosureIP23 indoorIP65 outdoor Dimensions H × W × D1750 × 1100 × 950 mmOn request Mass2550 kgOn request Also available open-type (IP00). Air-forced (AF) cooling available where the footprint has to come down. We quote indoor and outdoor together so you can compare size and price before you decide. Construction. Three-phase dry-type isolation transformer with enamelled copper windings and drilled copper bar terminals mounted at the bottom of the unit for cable longevity. Neutral available on the output for connection if required. Brass earth stud provided for connection. Supplied open (IP00), or fitted inside a powder-coated steel enclosure — vented for indoor (IP23) or sealed for outdoor (IP65) use, with panels to access terminals for hardwiring. ConfigurationDyn11 · 3-wire Delta to 4-wire StarOther available on request InsulationClass H — 180 °C StandardsAS/NZS 60076 AS/NZS 61558 Warranty5 years standard Lead Time GuaranteeConfirmed on order Australian madeBuilt in Dandenong South Options. Electrostatic screen led to an isolated terminal (typically recommended), ±2.5% and ±5% off-load tappings, winding temperature sensors, air-forced cooling, side gland plate, IP66 wiring chamber. Sends the part number and rating with your enquiry. | |||||
Beyond what’s in the above table
Each unit’s specs give you the dimensions, approx. mass, configuration, construction and standards. These apply across the range:
Frequency: 50 Hz or 60 Hz
Impedance: 2–4% Ez typical, or designed to a specified value
K-factor: K4 typical, higher for heavily non-linear loads
Cooling: Air natural (AN). Air forced (AF) available where the footprint has to come down
Temperature rise: <125 °C at 45 °C ambient
Ambient Temperature: −10 °C to 45 °C
Enclosures:
- IP23 vented steel for switchrooms and containerised plant.
- IP65 sealed steel on heavy-duty galvanised plinths for units sitting on a pad in the open.
- Open (IP00) where the transformer goes inside your own enclosure or skid.
Most battery storage auxiliary transformers end up IP65 or inside the existing containerised plant.
Custom ratings: The table is an excerpt of our standard range. If your auxiliary 690V to 415V load doesn’t land on one of those numbers, we build to it — custom transformer solutions.

What we need to quote
- Auxiliary load in kVA, or the connected equipment list
- Whether the 690V source is an inverter, a generator or a supply transformer
- Indoor, containerised, or outdoors on a pad
- Ambient temperature range, and altitude if above 1,000 m
- Space available, and how the unit gets into position
- Any specified impedance, vector group or project standards
If you only have a single line 690V to 415V and a site address, send that. Working the rest out is our job.
Enclosures for Your Three-Phase Transformer
Southern Transformers can supply your transformer open, or encase your three-phase transformer in an oyster grey powder-coated steel enclosure for hard wiring. Our standard enclosures are rated at IP23 (indoor), or IP65 (outdoor) for when more protection is necessary. Outdoor enclosures typically come with wiring chambers fitted to the side to house input/output terminals.
Check this useful IP rating table.
We also offer wall-mounted enclosures for smaller 3-phase isolation transformers up to about 5kVA.

Frequently Asked Questions
If you have a question that is not listed here, please contact us – we’re always happy to help.
For a straight 690V to 415V change with no isolation requirement, yes, and it will be smaller and cheaper. For an auxiliary supply that needs its own neutral and earth reference, or separation from an inverter bus, no. Tell us the application and we’ll tell you which one you need.
Add up the auxiliary load and allow headroom for starting currents and future additions, then pick the next size up in the table. If you send the equipment list we’ll size up your 690V to 415V transformer for you.
The table is an example of standard sizes from our range, not the limit. We build to whatever rating the job needs.
Yes. K4 is typical for this application, and we design to a higher K-factor where the load warrants it.
Yes — IP65 sealed enclosure on galvanised plinths, designed for pad-mounting and forklift handling. Outdoor dimensions and mass are against each unit in the table.
Air-forced cooling reduces the footprint where space is tight. Tell us the space you have and we’ll tell you what fits.
Every unit ships with a test report, FAT report where required, GA drawings and schematics, certificate of compliance, warranty statement and O&M manual.