Below are four Transformer calculators we use every day as a custom transformer manufacturer, we thought to share

Transformer sizing kVA from volts and amps, kW to kVA, and what a higher voltage can save you on a long cable run.

The sizing calculator goes a step further than most. Give it a rating and two voltages and it proposes an indicative unit — isolation and autotransformer (if applicable) side by side, with dimensions and mass for open-type, IP23 and IP65 — so you can see what you are actually fitting before you ask anyone for a price.

Transformer sizing

Enter the rating and the voltages. Line currents and star phase voltages are worked out for both sides, and an indicative unit is proposed.

Primary line current—
Secondary line current—
Primary phase voltage star only—
Secondary phase voltage star only—

—

Proposed indicative unit

Isolation transformer —
Open-type——
IP23 encased——
IP65 encased——
Autotransformer —
Open-type——
IP23 encased——
IP65 encased——

Dimensions are height × width × depth in millimetres, and masses are approximate. These figures are for reference only — the actual design, dimensions and mass are confirmed at enquiry. Open-type dimensions assume mounting in free air; advise us if the transformer is going inside a sealed or ventilation-restricted enclosure.

kVA from volts and amps

Three-phase. Use it to size from a nameplate or a measured load.

Apparent power—

The kVA is the same on both sides of a transformer, so one side is all you need. Take the result up to the sizing calculator for currents, dimensions and mass.

kW to kVA

Transformers are rated in kVA. If your load is quoted in kW you need its power factor.

Apparent power—

0.8 is the usual assumption for mixed industrial load. Motors and drives vary — use the figure on the nameplate if you have it.
Modern UPS, inverters and drives with power factor correction are typically 0.9 to 1.0.
Purely resistive load such as heating elements is unity (1.0).

Long cable runs — what a higher voltage saves

The same power at a higher voltage draws less current, so the cable gets smaller and the volt drop falls away — saving you hefty cable costs and the rework that comes with fixing volt drop after the fact.

Current at 415 V—
Current at 1,000 V—
Reduction in line current—

Step up to 1,000 V at the source, run the distance, step back down to 415 V at the far end. 1,000 V is still low voltage, so you avoid HV switchgear, HV cable and the approvals that come with them. More on step-up and step-down pairs.

The formulas. Three-phase line current I = kVA × 1000 ÷ (VL-L × √3) · Apparent power kVA = VL-L × I × √3 ÷ 1000 · Star phase voltage VL-N = VL-L ÷ √3 · Apparent from real power kVA = kW ÷ pf

How to size a transformer

1. Add up the load. Total the connected equipment in kVA. If it is quoted in kW, divide by the power factor — the kW to kVA calculator above does it.

2. Allow headroom. Motor starting current, anything you are likely to add later, and the ambient the transformer will sit in. Then take the next standard rating up.

3. Decide whether you need separation. An autotransformer shares one winding, so it is smaller, lighter and cheaper. An isolation transformer has two, which gives the load its own neutral and earth reference and a barrier against faults and noise on the supply. This is the decision that matters, and it is the one a calculator cannot make for you.

4. Check it fits. Dimensions and mass are not an afterthought on a 500 kg unit going into a switchroom or up onto a mezzanine. The calculator gives you both for all three enclosure options.

If you would rather we sized it, send the equipment list. That is a normal part of quoting, not an extra.

close up of inside transformer wiring chamber of a 1000v to 415v @ 15kVA transformer, shoing the screw terminals and earth stud
Terminals of a 3ph 1000V / 415V @ 15kVA 3ph isolation transformer
image of drilled bar terminals of a 3ph auto transformer 415V to 380V @ 125kVA. Showcasing the smaller physical size that can be created using an auto transofmrer over an isolation transformer
Example of the physical size of a 125kVA 3ph step down (autotransformer). Encased in an IP23 enclosure (480 x 480 x 480 mm @ 115 kg)

Worked Example

A 125 kVA unit stepping 415 V down to 380 V.

The input is 415V @ 174A output is 380V @ 190A (125kVA)

The autotransformer (pictured) is encased IP23 with dimensions: 480 x 480 x 480 mm @ 115kg.
The same 415V / 380V @ 125kVA IP23 specs in an isolation transformer: 1300 x 775 x 700 mm @ 720 kg approx.

An Isolation transformer: Galvanically separated Primary & Seconardy windings. Provides a fresh neutral and earth reference for the load, and a barrier between the site supply and your equipment.
An Autotransformer: has a common winding for both input and output, allowing a smaller, lighter, and more economical build compared to a fully isolated transformer. Best suited for applications where galvanic isolation is not necessary.

Significant differences in size, mass and naturally price, so worth considering the system they are going into.

Give us a call

Frequently Asked Questions

quality icon

Australian-Made. Built to Last

All Southern Transformers products are locally designed and manufactured for long service life, with full compliance to Australian Standards.

gears icon

Custom-Built for Industrial Demands

From commercial industries to major sectors, we tailor each transformer to meet the real-world needs of your application – no limitations.

agile icon

Delivered to Your Schedule without Compromise

We understand project timelines matter – Southern Transformers delivers transformers to meet your schedule, fast or slow, without cutting corners.

performance icon

5-year Warranty, 25+ year design life

Every transformer is designed and built to operate continuously at rated power for 25+ years, backed by an industry-leading standard 5-year warranty.