Electrical Design Summary
  • Voltages
    Up to 6.6 kV on the medium-voltage side, 415 V on the low side, either direction
  • Rating
    Up to 500 kVA
  • Configuration
    Dyn11 standard; YNd11, Dyn1 and other vector groups to suit the system
  • Frequency
    50 Hz, 60 Hz, or other
  • Construction
    Open-wound dry-type, enamelled copper windings, premium core steel
  • Insulation
    Class H — 180 °C
  • Impedance
    2–4% typical, or designed to a specified value
  • Efficiency
    Typically above 97.5%
  • Temperature rise
    Typically under 115 °C
  • Cooling
    Air natural (AN), or air forced (AF) where space is tight
  • Enclosures
    Open (IP00), IP23, IP65, or custom

Compliance
  • AS/NZS/IEC 60076
  • AS/NZS/IEC 61558
  • Every transformer is comprehensively Type Tested & Routine Tested
  • Standard 5-year Warranty, with a 25+ year design life

Documentation

Provided as Standard with Every Transformer:

  • Design stage:
    Transformer Specification
    Preliminary GA Drawing
    Schematic
  • Upon Order:
    Guaranteed leadtime
    Progress updates
  • On Completion
    AS60076 Test Report
    FAT Report
    5-year Warranty Statement
    GA Drawing as built
    O & M Manual

In order to provide you with the best MV/LV transformer solution for your requirements, the more information you can provide us, the better.

If you do not know specifics, thats fine – that’s what we’re here for. We’ve been around long enough to be able to evaluate most applications and recommend the right MV/LV transformer for your site and equipment.

Give us a call

close up of MV/LV transformer - 2800V isolated brass stud terminals on isolators. fitted to a 300kVA isolation transformer
Isolated Brass stud terminals on a 3ph isolation transformer 415V to 2800V @ 300kVA, fitted in IP23 enclosure
2x 200kVA isolation transformers IP65 - part numbers SD1000-200kVA-IP65 built for Tassal as a Step up, step down pair for TASSAL to run 1kV cable out to their feeding barges in Port Arthur Tasmania
Pair of 415V to 1000V 3ph isolation transformers. Designed to Step voltage up and back down to save on long cable run. IP65 enclosures
close up of screw terminals and rating plates on a 3ph isolation transformer 415V to 1000V @ 35kVA IP23. an example of a MV/LV transformer
3ph 415V to 1000V @ 35kVA screw terminals with ±% tappins on Primary for voltage adjustment.
IP65 transformer enclosure with IP66 wiring chamber fitted to the sides housing input/output terminals.
Example of IP65 enclosure with IP66 wiring chamber fitted to the sides to input/output terminals.
close up of inside transformer wiring chamber of a 1000v to 415v @ 15kVA transformer, shoing the screw terminals and earth stud
Screw terminals within IP66 wiring chamber of a 3ph 1000V to 415V @ 15kVA transformer, encased IP65.

Medium voltage on both sides is assessed on application rather than built to a standard design.

All three are legitimate. Which one suits depends far more on where the transformer is going and how standard the job is than on which is “better”.

Oil-filled gives the best cooling and the lowest cost per kVA at larger MV ratings, and it’s the default for utility-style pad-mount distribution. The cost is the oil: bunding and containment, fire separation, spill risk, and oil sampling for the life of the asset. On a lot of indoor and underground sites it simply isn’t permitted.

Cast resin encapsulates the windings in epoxy. It does very well in humid, dusty or chemically aggressive air, needs little maintenance, and is the usual choice where an indoor fire classification is specified. The trade-offs are that the moulds make one-off and non-standard units slow and expensive, and that an encapsulated winding can’t be repaired — if it fails, the unit is replaced.

Open-wound dry-type — what we build — has no oil, so no bunding, no containment and no restriction on indoor or underground installation. It can be rewound rather than replaced, which matters on a remote site or a long-life asset. And because there’s no tooling involved, a non-standard voltage, an unusual vector group, extra tappings or a specific footprint cost design time rather than a new mould.

The honest trade-off: in a genuinely harsh atmosphere, an open-wound unit needs the right enclosure around it where a cast resin unit might not. That’s what the IP65 option is for, and it’s a cheaper problem to solve than the ones the other two bring.

In short: if you’re buying a standard distribution transformer for an outdoor pad and bunding is no obstacle, oil is hard to beat on cost. If the job is project-specific, has to go somewhere oil can’t, or needs to be repairable in fifteen years’ time, dry-type is the one that fits.

3ph isolation transoformer 150kVA IP23 panels removed to show transformrer within
3ph custom transformer – 208V (Delta) to 480V (Star) @ 150kVA. Encased IP23
2x 3ph custom transformers 415V to 480V @ 170kVA autotransformer. Fitted in IP23, powdercoated black
2x 3ph custom transformers, 415V to 480V autotransformers, fitted out in IP23 enclosures for event management

 

Transformer Solutions Made Simple

Provide your project details and we’ll respond promptly with expert guidance tailored to your needs.

  (03) 9706 4202

Transformer Solutions

quality icon

Australian-Made. Built to Last

All Southern Transformers products are locally designed and manufactured for long service life, with full compliance to Australian Standards.

gears icon

Custom-Built for Industrial Demands

From commercial industries to major sectors, we tailor each transformer to meet the real-world needs of your application – no limitations.

agile icon

Delivered to Your Schedule without Compromise

We understand project timelines matter – Southern Transformers delivers transformers to meet your schedule, fast or slow, without cutting corners.

performance icon

5-year Warranty, 25+ year design life

Every transformer is designed and built to operate continuously at rated power for 25+ years, backed by an industry-leading standard 5-year warranty.

Step up, run the distance, step down

One of the most useful things you can do with a pair of these has nothing to do with the equipment at either end.

If you need to get power a long way across a site, running it at 415 V means large cable and volt drop you can’t design out. Step it up to 1,000 V at the source, run the distance at a third of the current, then step it back down to 415 V where it’s needed — and the cable gets substantially smaller and the volt drop goes away.

The reason this works well at 1,000 V is that it stays low voltage. You avoid HV switchgear, HV cable, HV-rated terminations and the approvals and competencies that come with them, while getting most of the benefit of transmitting at a higher voltage.

We build these as matched pairs, engineered together — the step-up unit and the step-down unit are designed as one job so the vector groups, impedances and earthing arrangements work with each other rather than being two transformers that happen to be on the same site.

Related reading: a smarter way to tackle long cable runs

What we need to quote

  • Supply voltage and whether it’s 3-wire or 4-wire
  • The voltage you need, and which way round
  • Load in kVA, or the connected equipment list
  • Indoors, outdoors, underground, or inside your own enclosure
  • Ambient temperature range, and altitude if above 1,000 m
  • Space available, and how the unit gets into position
  • Any specified impedance, vector group, fault level or project standard
  • Earthing arrangement required on the LV side

If all you have is a single line and a site address, send that.