Below are four Transformer calculators we use every day as a custom transformer manufacturer, we thought to share
Transformer sizing kVA from volts and amps, kW to kVA, and what a higher voltage can save you on a long cable run.
The sizing calculator goes a step further than most. Give it a rating and two voltages and it proposes an indicative unit — isolation and autotransformer (if applicable) side by side, with dimensions and mass for open-type, IP23 and IP65 — so you can see what you are actually fitting before you ask anyone for a price.
Transformer sizing
Enter the rating and the voltages. Line currents and star phase voltages are worked out for both sides, and an indicative unit is proposed.
—
Proposed indicative unit
Dimensions are height × width × depth in millimetres, and masses are approximate. These figures are for reference only — the actual design, dimensions and mass are confirmed at enquiry. Open-type dimensions assume mounting in free air; advise us if the transformer is going inside a sealed or ventilation-restricted enclosure.
kVA from volts and amps
Three-phase. Use it to size from a nameplate or a measured load.
The kVA is the same on both sides of a transformer, so one side is all you need. Take the result up to the sizing calculator for currents, dimensions and mass.
kW to kVA
Transformers are rated in kVA. If your load is quoted in kW you need its power factor.
0.8 is the usual assumption for mixed industrial load. Motors and drives vary — use the figure on the nameplate if you have it.
Modern UPS, inverters and drives with power factor correction are typically 0.9 to 1.0.
Purely resistive load such as heating elements is unity (1.0).
Long cable runs — what a higher voltage saves
The same power at a higher voltage draws less current, so the cable gets smaller and the volt drop falls away — saving you hefty cable costs and the rework that comes with fixing volt drop after the fact.
Step up to 1,000 V at the source, run the distance, step back down to 415 V at the far end. 1,000 V is still low voltage, so you avoid HV switchgear, HV cable and the approvals that come with them. More on step-up and step-down pairs.
The formulas.
Three-phase line current I = kVA × 1000 ÷ (VL-L × √3) ·
Apparent power kVA = VL-L × I × √3 ÷ 1000 ·
Star phase voltage VL-N = VL-L ÷ √3 ·
Apparent from real power kVA = kW ÷ pf
How to size a transformer
1. Add up the load. Total the connected equipment in kVA. If it is quoted in kW, divide by the power factor — the kW to kVA calculator above does it.
2. Allow headroom. Motor starting current, anything you are likely to add later, and the ambient the transformer will sit in. Then take the next standard rating up.
3. Decide whether you need separation. An autotransformer shares one winding, so it is smaller, lighter and cheaper. An isolation transformer has two, which gives the load its own neutral and earth reference and a barrier against faults and noise on the supply. This is the decision that matters, and it is the one a calculator cannot make for you.
4. Check it fits. Dimensions and mass are not an afterthought on a 500 kg unit going into a switchroom or up onto a mezzanine. The calculator gives you both for all three enclosure options.
If you would rather we sized it, send the equipment list. That is a normal part of quoting, not an extra.
Worked Example
A 125 kVA unit stepping 415 V down to 380 V.
The input is 415V @ 174A output is 380V @ 190A (125kVA)
The autotransformer (pictured) is encased IP23 with dimensions: 480 x 480 x 480 mm @ 115kg.
The same 415V / 380V @ 125kVA IP23 specs in an isolation transformer: 1300 x 775 x 700 mm @ 720 kg approx.
An Isolation transformer: Galvanically separated Primary & Seconardy windings. Provides a fresh neutral and earth reference for the load, and a barrier between the site supply and your equipment.
An Autotransformer: has a common winding for both input and output, allowing a smaller, lighter, and more economical build compared to a fully isolated transformer. Best suited for applications where galvanic isolation is not necessary.
Significant differences in size, mass and naturally price, so worth considering the system they are going into.
Frequently Asked Questions
Total the connected load in kVA, allow headroom for motor starting and future load, then take the next standard rating up. The calculator above does the arithmetic and proposes a unit. If you send the equipment list we will size it for you.
Because a transformer does not know what it is feeding. Its limits are the current its windings can carry and the voltage its insulation can stand, and those two multiplied give volt-amps. How much of that becomes real power depends on the load’s power factor, which is the load’s business, not the transformer’s.
Line current = kVA × 1000 ÷ (line voltage × √3). For 200 kVA at 415 V that is 278 A. The reverse, kVA = V × I × √3 ÷ 1000, gives the rating from a measured load.
An autotransformer shares one winding: smaller, lighter and cheaper, and the right answer when you only need to change voltage. An isolation transformer has separate windings and gives the load its own neutral and earth reference plus a barrier against faults and noise. If the equipment, the standard or the earthing arrangement calls for separation, it is isolation. Tell us what it is feeding and we will tell you which the application needs.
They come from our own design data for standard units, so they are a sound guide for planning space and lifting. They are indicative only — the actual design is confirmed at enquiry, and a non-standard voltage, vector group or enclosure changes them.
Yes. Above 690 V, above 600 kVA, or any non-standard arrangement, the unit is engineered to the job rather than taken off a standard frame. See custom transformer solutions and MV/LV isolation transformers.
These are the ones we reach for ourselves.
The standards. AS/NZS 3008.1.1 covers cable selection, current carrying capacity and volt drop — the obvious next step once you have the current off the calculator above. AS/NZS 3000, the Wiring Rules, covers the installation. Our transformers are built and routine tested to AS/NZS 60076 and AS/NZS 61558. All available from Standards Australia.
Cable sizing and volt drop. ELEK publish free AS/NZS 3008 cable sizing and volt drop calculators. Check which edition of the standard a calculator is built on before you rely on it for a design — at the time of writing theirs cite the 2017 edition.
Sizing a transformer. Our own custom transformer solutions page sets out what we need to quote a non-standard unit. If you would rather we sized it, send the equipment list.
We have deliberately not published a cable sizing tool. Cable selection is safety critical and it is a cable specialist’s job, not a transformer manufacturer’s. The calculators on this page cover what we build and what we are competent to stand behind.
Australian-Made. Built to Last
All Southern Transformers products are locally designed and manufactured for long service life, with full compliance to Australian Standards.
Custom-Built for Industrial Demands
From commercial industries to major sectors, we tailor each transformer to meet the real-world needs of your application – no limitations.
Delivered to Your Schedule without Compromise
We understand project timelines matter – Southern Transformers delivers transformers to meet your schedule, fast or slow, without cutting corners.
5-year Warranty, 25+ year design life
Every transformer is designed and built to operate continuously at rated power for 25+ years, backed by an industry-leading standard 5-year warranty.